        電動(dòng)執(zhí)行器的維修和保養(yǎng)(電動(dòng)執(zhí)行器)
        發(fā)布時(shí)間:2020-07-28 15:13:13

        Common faults and elimination methods of electric actuators

        malfunction

        the reason

        elimination method

        1. The motor cannot start

        1. Power failure or lack of phase

        1. Check the power supply

        2. Low power supply voltage

        1. Check the voltage

        3. The action of the overheat protection switch embedded in the motor coil (motor overheating)

        3. See if the fault can be eliminated after the motor temperature drops

        4. The valve or actuator itself is stuck

        4. Try manual operation with actuator handwheel

        2. The motor stops during the switch operation

        1. The load is too large, so that the force protection switch acts

        1. Try to increase the setting value of torque protection

        2. The action of the overheat protection switch embedded in the motor coil (motor overheating)

        2. See if the fault can be eliminated after the motor temperature drops

        3. Control circuit board failure

        3. Replace the circuit board

        3. The electrical limit switch cannot limit

        1. Motor reverse

        1. Try to replace the motor wiring, or replace the split-phase capacitor, otherwise replace the motor

        2. The limit switch is damaged

        2. Replacement limit development

        3. The limit position is not adjusted

        3. Readjust

        4. The circuit board is damaged

        4. Replace the circuit board

        4. The motor runs but the valve does not move

        1. The switching mechanism is abnormal

        1. Disassembly inspection

        2. Connection problems

        2. Check the connection

        Fifth, do not move manually

        1. The switching device is not closed

        1. Switching device

        2. Mechanical stuck

        2. Eliminate the cause of the death

        Six, valve stem vibration at startup

        The stem nut is loose or improperly tightened

        Remove the stem cover or pipe plug and tighten the lock nut

        7. Poor insulation

        Into the rain (poor sealing of the wire inlet)

        1. Repair sealing parts

        2. Drying electrical components and motors

        3. Pay attention to the cable inlet seal

        8. Oil leakage

        1. Damaged seal

        1. Check and repair the seal

        2.The ambient temperature is high, and the internal pressure of the main box increases

        2. Loosen the screws that do not affect the work, (preferably oil plug) exhaust

        Nine, on-site control is normal, remote control is not

        1. The circuit board is damaged

        1. Replace the circuit board

        2. The control signal line is damaged

        2. Check the control signal cable

        3. The control signal is connected incorrectly

        3. Check the wiring

        Ten, on-site control is normal, the remote control valve position display disappears

        1. The position sensor is broken

        1. Check the sensor

        2. Itinerary is not set

        2. Reset the itinerary

        3. The circuit board is broken

        3. Replace the circuit board

        11. One-way action

        1. Circuit board failure

        1. Replace the circuit board

        2、One-way limit

        2. Re-adjust the limit

        3、Damaged motor

        3. Replace the motor


        Maintenance and maintenance of electric actuators (electric actuators):

        Electric actuators (electric actuators) are electromechanical integration products, mainly composed of motors, bearings, gear transmission systems and electronic parts. According to the reliability data published by the US military standard MIL-HDBK-338, mechanical failures of electric actuators (electric actuators) are mainly concentrated on bearings. In terms of electrical appliances, the problem is mainly on the control circuit board, and sometimes the motor also fails. Among the motor failures: winding failure accounts for 20%, bearing failure accounts for 45%, and slip ring, brush, and commutator damage accounts for 5%. Others account for 30%; in bearing failures: lubricant deterioration and disappearance account for 45%, pollution account for 30%, erosion account for 5%, misadjustment accounts for 5%, corrosion accounts for 5%, others account for 10%. It can be seen that good maintenance management can improve the reliability and effectiveness of electric actuators.

        1. Strengthen the cleanliness management of lubricating oil The biggest feature of electric actuators is the need to use lubricating oil, whose viscosity changes with oil temperature. If the viscosity is too low, the wear of the transmission components such as the turbine worm and gear will increase, which will reduce the transmission accuracy; if the viscosity is too high, the action will be bad. The management of the cleanliness of lubricating greases is more difficult. The wear of turbine worms and gears, the penetration of impurities and moisture generated by aging, the shedding of internal coatings, and corrosion will affect the cleanliness of lubricating oil.

        2. Eliminate the leakage of lubricating grease in time. Due to the high operating frequency and speed of the electric actuator (electric actuator), it is difficult to avoid impact. This is an important reason for the leakage of lubricating grease. Once the lubricating grease leaks, it needs to be resolved in time.

        3. Improve the working environment and operating conditions of electric actuators (electric actuators). The reliability and life of electric actuators (electric actuators) are directly related to its use, environment, personnel knowledge and other factors. Only by improving its working environment and conditions of use in maintenance and management, and putting people first, can it extend its service life.

        4. Special maintenance should be strengthened in the early stage of the failure. Among all the failures of the electric actuators, the proportion of the initial failures is generally relatively high. Most of the initial faults are caused by preliminary errors in design, manufacturing, and installation. The discovery of these initial faults requires a certain amount of effort, and it takes time to solve them. Therefore, maintenance management should be strengthened during the initial failure period.

        5. Do a good job of data management to prevent accidental failures of electric actuators (electric actuators) are generally difficult to predict. In order to prevent sporadic failures, it is necessary to regularly check and maintain, and master the maintenance data and historical file data at a certain stage, which is very important for the accurate implementation of failure judgment and daily maintenance.

        6. Improve the professional knowledge of the operation and maintenance personnel The mastery of the professional knowledge of the operation and maintenance personnel directly affects the maintenance management. In recent years, due to changes in the structure of operation and maintenance personnel, they have greatly improved their knowledge and technology of electric actuators. However, many operation and maintenance personnel still lack the professional knowledge and technology they deserve. Most of the on-site operation and maintenance personnel are in a state of "seemingly understand but not understanding" about electric actuators, which is also the weak link of maintenance management. In order to facilitate the operation and maintenance personnel to carry out on-site maintenance and management, we must have advanced awareness in the design of electric actuator systems, fully consider the implementation of maintenance and management, and strive to achieve: the system should be simplified, the simple system failure rate is low, and maintenance management Easy; high degree of standardization, good interchangeability, easy to repair; integration, combination, convenient adjustment and inspection; introduction of new technologies such as fault diagnosis and positioning, fault tolerance/correction.

        7. Since the control circuits of electric actuators (electric actuators) are damaged most, it is necessary to increase the service life of the control circuit board, and the control circuit boards of electric actuators (electric actuators) are damaged greatly. Most of them are caused by water ingress or dampness, and the ambient temperature is too high. Therefore, it is necessary to ensure that the electric control room of the electric actuator (electric actuator) is well sealed, and try not to let water get in. Try to make a canopy for the electric actuator (electric actuator) if possible. Most actuators can only reach IP67, this protection can only be drenched in the rain for a short time and cannot be exposed to heavy rain.


        亚洲天堂激情| 人妻少妇精品无码专区| 久久久久国产精品| 狠狠色综合网久久久久久| 一边摸一边做爽的视频17国产 | 无码GOGO大胆啪啪艺术| 国产欠欠欠18一区二区| 国产在线无码视频| 欧美人妻少妇| 欧美性xxxxx极品少妇| 国产女人18毛片水真多| 成人特黄a级毛片免费视频| 国产精品无码制服丝袜| 日韩成人在线播放| 50岁人妻丰满熟妇ΑV无码区| 无码熟妇AvDvD| 高潮流白浆潮喷在线播放视频 | 宝贝腿开大点我添添公口述视频| 亚洲国产综合人成综合网站 | 欧美日韩啪啪| 久久影院中文字幕| 亚洲精品9999久久久久| 激情综合婷婷| 成人欧美一区二区三区的免费| 日韩午夜福利无码专区A| 尤物视频在线| 2021久久伊人精品中文字幕有| 欧美特黄一级高清免费的香蕉| 亚洲国产欧美一区二区三区| 国产精品无码专区在线观看| 欧美日韩一区在线| 成人艳情一二三区| 无码熟妇人妻AV在线影院| 国产AV激情无码久久| 免费吃奶摸下激烈视频| 无码人妻精品一区二| 日本一区二区三区精品福利视频| 一本一本久久A久久精品综合| 久久精品水蜜桃AV综合天堂| 国产福利在线永久视频| 大地资源免费视频观看|